Radio ISO Prefabricated Containers
Agency: | DEPT OF DEFENSE |
---|---|
Level of Government: | Federal |
Category: |
|
Opps ID: | NBD00159834095635722 |
Posted Date: | Mar 29, 2023 |
Due Date: | Apr 13, 2023 |
Solicitation No: | FA875123R0004 |
Source: | https://sam.gov/opp/6eb7655ced... |
Procurement Technical Assistance Centers (PTACs) are an official government contracting resource for small businesses. Find your local PTAC (opens in new window) for free government expertise related to contract opportunities.
- Contract Opportunity Type: Presolicitation (Original)
- All Dates/Times are: (UTC-04:00) EASTERN STANDARD TIME, NEW YORK, USA
- Original Published Date: Mar 29, 2023 01:02 pm EDT
- Original Response Date: Apr 13, 2023 03:00 pm EDT
- Inactive Policy: 15 days after response date
- Original Inactive Date:
-
Initiative:
- None
- Original Set Aside:
- Product Service Code: 5450 - MISCELLANEOUS PREFABRICATED STRUCTURES
-
NAICS Code:
- 332311 - Prefabricated Metal Building and Component Manufacturing
-
Place of Performance:
Rome , NY 13441USA
This is a Notice of Proposed Contract Action under the FAR Part 12 Acquisition of Commercial Items, and FAR Part 13 Simplified Acquisition Procedures. This notice is for information only; a solicitation will not be issued. THIS IS NOT A REQUEST FOR QUOTATION. No contract will be awarded on the basis of offers received in response to this notice. The associated North American Industry Classification System (NAICS) code is 332311 with a small business size standard of 750 employees.
AFRL requires twelve (12) prefabricated containers meeting the following specifications:
Prefabricated Container, 8’ x 20’ x 8’6”H
Structure Elements
o 20' Standard ISO Shipping Container with ISO corners and forklift pockets
o One (1) insulated partition wall to divide the container into a 9’9” x 6’9” insulated work room and an 8’6” x 8’ uninsulated storage/mechanical room.
- One (1) Interior, Insulated, 3070, Flush Swing Door, with door gear installed in the partition wall.
- Work Room
- Insulation: Walls, roof, floor R-18
- Walls to be covered by Textured FRP
- Ceiling to be covered by Textured FRP
- Storage/Mechanical room
- No Insulation
- Walls to be standard container corrugated steel
- Ceiling to be standard container corrugated steel
- Container cargo doors open to access the storage room
o Floor to be epoxy in the storage room and VCT tile in the workroom
o Brackets for anchoring to foundation.
o One (1) Painted Steel counter/workbench (66” wide x 30” deep)
o Steel sheeted belly pan
Electrical, HVAC, Data
o 12-gauge minimum copper wiring in 1/2” minimum EMT surface mounted and attached to surface mounted 4x4 boxes.
o One (1) Circuit Breaker Box, 125 Amp, 12 Spaces with 4 Circuits
o Two (2) single pole switches
- One (1) in each room
o Six (6) 115V duplex receptacles
- Five (5) in the workroom and One (1) in the storage room
o One (1) 115V exterior GFCI duplex receptacle
o Two (2) 220V Outlets
o Four (4) LED Light Fixtures
- Two (2) in each room
o One (1) Electrical Disconnect
o One (1) Manual Transfer Switch,120/240V, Single Phase
o One (1) Uninterruptible Power Supply System, 16kVA/12.8kW, 120/240V Single Phase, 6-minute battery at full load
o One (1) Surge Protection System
o One (1) weld-on grounding stud for attachment to customer provided/installed grounding rod.
o One (1) Bard HVAC unit, 1 ton cooling, 5kW Heating
o One (1) wall mounted dehumidifier with built-in humidistat.
- Includes condensate drain.
o Two (2) 18” W x 12” H Stormproof Louver vents w/ insect screens
- For ventilation in the storage room
Miscellaneous
o Two (2) open frame server racks 28.875” x 36U
o One (1) Cable management system
o One (1) Vidmar 6 drawer lockable cabinet 27.75” x 60”
o Two (2) padded folding chairs
o One (1) wall mounted first aid kit
o One (1) toolkit
o One (1) 6’ little giant ladder w/ wall mount
o One (1) wall mounted, 15A, 45’ retractable cord reel
o Two (2) 3’ long sections of Unistrut for securing the antennas next to the HVAC unit.
o Four (4) container castor wheels, urethane on iron, 10,000 lb rating
- Includes one set of 4 castors for use on one of the containers at a time
Other
o Container fully painted to protect from corrosion
o Building ships assembled FOB Destination Shipping to Rome, NY
The Government intends to negotiate a sole source contract with:
UH Structures Inc.
dba Ebtech Industrial
2241 Industrial Drive
Connellsville, PA 15425
The Government has determined that no other source has commercial offerings that can meet this requirement. The containers will be used to house and operate miliary and commercial radios, as well as computer equipment in support of a Government program. The required specifications include all the options required to allow the container to keep all the equipment safe from the elements to include holding the internal environment of the container at a certain temperature and humidity in varying climates. Additionally, the containers will need to be provided to AFRL/RI ready to connect external power and be ready to populate with all the radio and computer equipment. Ebtech Industrial has built similar containers for the DoD at locations all over the world and has experience in building shelters that will operate in the climates required, and is the only known vendor who can satisfy the requirement.
This is a notice of proposed contract action and not a request for competitive proposals; however, all responsible sources may submit a capability statement or proposal, which shall be considered by the agency. All inquiries should be sent by email to Ashley.Ellinger@us.af.mil. Responses must be submitted by the date/time listed on the notice. Any response to this notice must show clear and convincing evidence that competition would be advantageous to the Government in future procurements.
Responses received will be evaluated; however a determination by the Government not to compete the proposed procurement based upon responses to this notice is solely within the discretion of the Government. The Government anticipates an award date on or before 31 May 2023.
A Sole Source Justification will be attached to the subsequent Notice of Award in accordance with applicable regulation.
- CP 315 330 7298 26 ELECTRONIC PKWY BLDG 106
- ROME , NY 13441-4514
- USA
- Ashley Ellinger
- ashley.ellinger@us.af.mil
- Mar 29, 2023 01:02 pm EDTPresolicitation (Original)
TRY FOR FREE
Not a USAOPPS Member Yet?
Get unlimited access to thousands of active local, state and federal government bids and awards in All 50 States.